Product Details:
Payment & Shipping Terms:
|
| Name: | Toughened Glass High Voltage Suspension Insulator | Mechanical Damage Load: | >300KN |
|---|---|---|---|
| Battering Load: | >1017KN | Electromechanical Load Test Value: | 225KN |
| Weight: | 10.7kg | Nominal Height: | 195mm |
| Nominal Diameter: | 320mm | Minimum Nominal Creepage Distance: | 485mm |
| Highlight: | transmission tools,transmission tools and equipment |
||
Transmission Line Stringing Tools Standard Type 130kv Anti-fouling Toughened Glass High Voltage Suspension Insulator
Product parameters
| Model | BYLXY-70 | BYLXY1-70 | BYLXY-100 | BYLXY-120 | BYLXY3-160 | BYLXY3-210 | BYLXY-240 | BYLXY-300 | |
|
Mechanical damage load≥ KN |
70 | 70 | 100 | 120 | 160 | 210 | 240 | 300 | |
|
Battering load≥ KN |
565 | 565 | 678 | 678 | 1017 | 1017 | 1017 | 1017 | |
|
Electromechanical load test value/h KN |
52.5 | 52.5 | 75 | 90 | 120 | 157.5 | 180 | 225 | |
|
Nominal Height H mm |
127 | 146 | 146 | 146 | 155 | 170 | 170 | 195 | |
|
Nominal diameter of insulator D mm |
255 | 255 | 255 | 255 | 280 | 280 | 280 | 320 | |
|
Minimum nominal creepage distance mm |
320 | 320 | 320 | 320 | 380 | 390 | 390 | 485 | |
|
Peak voltage tolerance for lightning full - wave shock kv |
≥100 | ≥100 | ≥100 | ≥100 | ≥105 | ≥105 | ≥105 | ≥105 | |
|
Effective value of power frequency voltage≥ kv |
1min wet resistance | 40 | 40 | 40 | 40 | 42 | 42 | 42 | 45 |
| Breakdown | 130 | 130 | 130 | 130 | 130 | 130 | 130 | 130 | |
| Weight/set (kg) | 3.77 | 3.78 | 4.1 | 4.2 | 6.2 | 6.7 | 6.8 | 10.7 | |
Product description
Feature
![]()
Contact Person: Mr. Green Lu
Tel: +86 18036062799